AC&M


               





Power Transducer Table

TYPE MODEL INPUT OUTPUT AUX POWER
AC Voltage TDV A. 0~150VAC
B. 0~300VAC C. 0~600VAC
A. 0~10mA DC
B. 0~20mA DC
C. 4~20mA DC
D. 0~5V DC
E. 1~5V DC
F. 0~10V DC
Y. Other
A. 110/220V AC
B. 24V DC
C. 110V DC
D. 125V DC
E. Self Power
TDV3
AC Current TDA A. 0~1A AC
B. 0~5A AC
C. 0~10A AC
TDA3
Watt TDW A. 1 • 2W
B. 3 • 3W
C. 3 • 4W
D. Other
Var TDQ
Watt/Var TDWQ A. 110V
B. 220V
Y. Other
Power Factor TDPF
Watthour TDWH A. 1Pulse/1WH B.10Pulse/1WH
Varhour TDQH A. 1A
B. 5A
Watt/Watthour TDWWH A. 50Hz
B. 60Hz
Var/Varhour TDQQH
Frequency TDF 30~600V AC 50 or 60 Hz Same as V, A, W, Var, PF


Power Transducer Specifications
Input Burden   : 0.1VA/60Hz at 150V AC; Self-Power Mode   2VA at 150V AC.
Input Range   : Normal Voltage 110V, Effective Range   85~150V.
  Normal Voltage 220V, Effective   Range   160~300V.
  Normal Current 5A, Effective Range 0~7.5A.
  Normal Current 1A, Effective Range 0~1.5A.
Input Over : Normal AC 110V, Voltage Over 500V   Continuous. Self-Power   Mode 150V AC Maximum.   Normal AC 5A. Current Over 15A   Continuous; 50A 10 Sec/Hour; 400A 0.5   Sec/Hour.
Output Load : DC Current Mode : 10VDC Maximum, DC   Voltage Mode :   10mA Maximum.
Output of WH or VarH : Open Collect Type, Effective Range   5~30V DC, 5~100mA.
Output Protection : Without Damage for Output Open or Short   Circuit.
Dielectric Strength : 2.6KV AC / Min between Input/Output/Power/Case.
Impulse : 4KV 1.2x50 uS. ANSI C37.90a/1983. DIN IEC 255 4.
Common Mode Rejection : 120db, 50/60 Hz.
Stability : 0.2%/Year.
Calibration : SPAN and ZERO ±10%.
Response Time : 400mS, 0 ~ 99%.
Ripple : 0.5%rms Max.
Magnetic Effect : DIN - IEE688 0.05% Change 10" Center   100A Turn.
Temperature Coefficientt : 100ppm /°C          From 0~60°C
Operation Condition : 10°C ~ + 65°C 20 ~ 95% RH Non-Condensed.
Storage Condition : -40°C ~ + 75°C 20 ~ 95% RH Non-Condensed.
Power Supply : Dual Power 110/220V AC or DC ±20%,   50/60Hz.
Aux. Power Effect : 0.01% / V
Housing material : ABS Plastic, Self-Extinguishing to UL   Subject 94 Class V-O.
Mounting : DIN Rail or Wall Mounting.


Microprcessor Digital Meter Table

TYPE MODEL LED DISPLAY DIGITS OUTPUT AUX POWER
AC Voltage DMV 4 1/2 Digits = 19999 Counts Programmable A. 0~10mADC
B. 0~20mADC
C. 4~20mADC
D. 0~5V DC
E. 1~5V DC
F. RS-485
Y. Other
A.110/220V     AC
B. 24V DC
C. 110VDC
D. 125V/DC
AC Current DMA
Watt DMW
Var DMQ
Watthour DMWH Watt, Var, DC Watt, Watt Demand:
4 1/2 Digits - 19999 Counts Programmable

Wathour, Varhour,
DC Watthour, Flow : 7 Digits = 9999999 Counts
A.1Pulse/1WH B.10Pulse/1WH
Varhour DMQH
Watt/Watthour DMWWH
Var/Varhour DMQQH RS-485
Watt Demand/WH DMM A.1Pulse/1WH
B.10Pulse/1WH
DC Watt/Watthour DMDWWH
Flow DML
Power Factor DMPF -0.500~1.000~+0.500  A. 0~10mADC
B. 0~20mADC
C. 4~20mADC
D. 0~5V DC
E. 1~5V DC
F. RS-485
Y. Other
Frequency DMF 4 1/2 Digits + 19999 Counts
DC Rate DME
Current Loop (2 Wire) DMS
DC Voltage, Current DMD
RTD Temperature DMR
T/C Temperature DMT
Load Cell DMB
RPM DMU
Potentiometer DMP
RS-485 DMG NONE
DC Current Stimulating DMX 4~20mA ADJ.


Microprocessor Digital Meter Specifications
 
Input Burden   : Voltage 0.2VA at 120V, Current 0.3VA at 5A   60Hz.
Input Overload   : 3 Rated Continuous at 120V AC.
  3 Rated Continuous at 5A AC.
  50 Rated 1 Sec., 80 Rated 0.5 Sec.
Dielectric Strength   : AC 2.6KV/Min., Input/Power/Case. DIN IEC 688.
Stability   : Long Term Draft 0.2%/year.
Temperature Coefficient   : 100ppm /°C From 0~60°C.
Response Time   : 1 Sec.
Analog Output Load   : Isolate Type. DC Current Mode : 7V DC Max., DC Voltage Mode : 5mA DC Max.
  Output Range User Selectable.
Digital Output Load   : Dual Setting & Contact Points, Setting Function User   Selectable.
Setting Function   : Isolate Type, RS-485 Output, 1200, 2400, 4800, 9600,   19200 Baud Rate User Selectable
Setting Range   : ±19999 Counts User Selectable.
Dead Band   : 0 ~ 9999 Counts User Selectable.
Time Delay   : 0 ~ 99 Sec, Counts User Selectable.
SPDT Capacity   : AC 120V 5A, 250V 3A, DC 24V 3A.
Stability   : 0.2%/Year.
Operating Condition   : - 10°C ~ +55°C 20 ~ 95% RH Non-Condensed.
Storage Condition   : - 40°C ~ +75°C 20 ~ 95% RH Non-Condensed.
Power Supply   : Dual Power 110/220V AC or DC ±20%, 50 /   60Hz.
Outline Dimension   : 1/8 DIN 96W x 48H x 135D mm.
Mounting   : Panel Flush Mounting.


Industrial Transmitter Table

TYPE MODEL INPUT OUTPUT AUX POWER
DC Isolating TMD 1. 0~10mADC
2. 0~20mADC
3. 4~20mADC
4. 0~5VDC
5. 1~5VDC
6. 0~10VDC
7. Other
1. 0~10mADC
2. 0~20mADC
3. 4~20mADC
4. 0~5V DC
5. 1~5V DC
6. 0~10V DC
7. Other
1. 110V AC
2. 220V AC
3. 24V DC
4. 110V DC
5. 125V DC
TMD2
TMD3
TMD4
RTD Temperature TMR 1. PT1000
2. CU10
RTD Temperature TMR2
RTD Temperature TMR3
T/C Temperature TMT K,E,J,T,R,S,B
Load Cell TMB Various mV DC
Frequency to DC TMF Open Collect etc.
DC to Frequency TMG Same as TMD Various Hz
DC Power Supply TMX 110 or 220V AC 6V; 12V; 24V DC
Current Loop
(2 Wire)
TMS 4~20mA DC Same as TMD
TMS2
TMS3


Specifications Industrial Transmitter
 
Input Impedance   : Voltage Input 1M , Current Input  50
Insulation Resistance   : 100M / 500V DC.
Output Strength : DC Current Mode : 10VDC Maximum, DC   Voltage Mode :   10mA Maximum.
Dielectric Strength : AC 1500V / Min. between Input / Output /   Power.
Maximun Input Over : 2V DC Range 300V rms Continuous.
  2V DC Range 150V    rms Continuous.
  20mA DC Range 150mA Continuous.
Linearty & Repeatability : 0.1% Typical.
Common Mode Rejection : 120db DC to 60Hz.
Stability : 0.2%/Year.
Adjustments : SPAN and ZERO ± 10% Minimum.
Response Time : 400mS.
Ripple : 0.1% rms RO.
Temperature Coefficient : 100ppm / °C From 0~60°C;
   50ppm /25°C ±5°C.
Operating Storage

: - 5°C ~ + 55°C 20 ~ 95% RH Non-Condensed.

Storage Condition : - 10°C ~ + 70°C 20 ~ 95% RH Non-Condensed.
Power Supply : AC or DC ± 20%.
Aux. Power Effect : 0.03% / V.
Mounting : DIN Rail or Wall Mounting.